3RN2013-2GW30 Thermistor motor protection relay Standard AC/DC 24-240V 2CO

Back| Overview|Product 26 of 78 in this category Prev|Next
3RN2013-2GW30 Thermistor motor protection relay Standard AC/DC 24-240V 2CO
For a larger view click on the thumbnail
3RN2013-2GW30 Thermistor motor protection relay Standard AC/DC 24-240V 2CO
3RN2013-2GW30 Thermistor motor protection relay Standard AC/DC 24-240V 2CO
3RN2013-2GW30 Thermistor motor protection relay Standard AC/DC 24-240V 2CO
Shipping time: 5 working days* 5 working days*
Stock quantity: 0 pcs. / order item
Product no.: 3RN2013-2GW30
GTIN/EAN: 4047621006772
MPN: 3RN2013-2GW30
Weight: 0.185 kg
Manufacturer: SIEMENSMore products of: SIEMENS
148,66 €
19 % VAT incl. excl. Shipping costs
Netto:124,92 €
* Valid for shipments within Germany.
Delivery times to other countries and information how to calculate see here


SIEMENS

  • Details
  • Data sheet
  • Features

Products description

SIEMENS 3RN2013-2GW30 SIRIUS Monitoring Relays Thermistor Motor Protection

 

Thermistor motor protection relay, Standard evaluation unit, 22,5mm enclosure, spring-type terminal, Control supply voltage: AC/DC 24-240 V, 2-change-over contact gold-plated, 2 LEDs (Ready/Tripped), Reset: Manual/Auto/Remote, Safe galvanic isolation, Test/reset button, Wire break monitoring, Short circuit monitoring, non-volatile, with ATEX approval

 

General Description

Thermistor motor protection devices are used for direct monitoring of the motor winding temperature. For this purpose, the motors are equipped with temperature-dependent resistors (PTC) that are directly installed in the motor winding and abruptly change their resistance at their limit temperature.

Versions

SIRIUS 3RN2 thermistor motor protection relays are available in the following versions:

  • Compact trip units 3RN2000
  • Compact/standard trip units 3RN2010
  • Bistable trip units 3RN2012-.BW31
  • Standard trip units with ATEX approval 3RN2011, 3RN2012-...30, 3RN2013
  • Trip units with ATEX approval and 2 sensor circuits for warning and disconnection 3RN2023

They comply with

  • IEC 60947-8. Low-voltage switchgear and controlgear – Part 8: "Control units for built-in thermal protection (PTC) for rotating electrical machines"
  • IEC 61000-6-2, IEC 61000-6-4. "Electromagnetic compatibility for industrial-process measurement and control equipment"

The 3RN2 thermistor motor protection relays with ATEX approval fulfill SIL1 in compliance with EN 50495.

The terminals of the auxiliary contacts are designated in accordance with EN 60947-1.

3RN2 evaluation units are suitable for snap-on mounting onto TH 35 standard mounting rails according to IEC 60715 or for screw fixing using an adapter (accessory).

Benefits

  • Thanks to direct motor protection, overdimensioning of the motors is not necessary
  • No settings on the device are necessary
  • Solid-state compatible output thanks to versions with hard gold-plated contacts
  • Rapid error diagnosis thanks to versions that indicate open and short circuits in the sensor circuit
  • All versions with removable terminals
  • All versions with screw or spring-type terminals with push-in functionality

Application

Direct motor protection through temperature monitoring of the motor winding offers 100% motor protection even under the most difficult ambient conditions, without the need to make adjustments on the device. Versions with hard gold-plated contacts ensure, in addition, a high switching reliability that is even higher than an electronic control.

Motor protection:

  • At increased ambient temperatures
  • When switching frequency is too high
  • When start-up and braking procedures are too long

ATEX approval for operation in areas subject to explosion hazard

The SIRIUS thermistor motor protection relays 3RN2011, 3RN2012-...30, 3RN2013 and 3RN2023 for PTC sensors are certified according to ATEX Ex II (2) G and D for environments with explosive gas or dust loads.

Motor protection using current- and temperature-dependent protective devices

IEC 60204 stipulates that motors must be protected from overheating at a rating of 0.5 kW and higher. The protection can take the form of overload protection, overtemperature protection or current limiting.

For motors with frequent starting and braking and in environments where cooling may be impaired (e. g. by dust), it is recommended to use the overtemperature protection option in the form of a protective device coordinated with this mode of operation. A good choice in this case is the use of 3RN2 thermistor motor protection devices.

On rotor-critical motors, overtemperature detection in the stator windings can lead to delayed and hence inadequate protection. In this case the standards stipulate additional protection, e. g. by means of an overload relay.

This combination of thermistor motor protection and an overload relay is recommended for full motor protection in case of frequent starting and braking of motors, irregular intermittent duty or excessive switching frequency. To prevent premature tripping of the overload relay in such operating conditions, a higher setting than that normally required for the operational current is chosen. The overload relay then performs the stall protection, and the 3RN2 thermistor motor protection relay monitors the temperature of the motor windings.

Datenblatt: 3RN2013-2GW30 Thermistor motor protection relay Standard AC/DC 24-240V 2CO

Product Features

Model:Standard
Supplement:, Safe galvanic isolation
Connection:spring-terminal
Control supply voltage:AC/DC 24-240 V
Contact:2-CO gold plated
Reset:Manual/Auto/Remote
Diagnosis:2-LED (Ready/Tripped)
Monitoring:Wire break/short circuit
Dimensions:Width 22,5 mm
Back| Overview|Product 26 of 78 in this category Prev|Next