Wago 750-306 WAGO-I/O-SYSTEM 750 Fieldbus Coupler
Fieldbus Coupler deviceNet, Baud rate: 125/250/500 kbaud, Buscoupler connection: female connector 231-305/010-000/050-000 included in scope of supply, no. of I/O modules: 64, input process image max.: 512 Byte, output process image max.: 512 Byte, no. of couplers connected to Master: 64 with Scanner
The ECO fieldbus coupler is designed for applications with a reduced scale I/O requirement.
Using digital only process data or small amounts of analogs, while retaining all of the choice that’s offered by the Series 750 I/O.
The coupler has an integrated supply terminal for the system voltage.
The field power jumper contacts are supplied via a separate supply module.
The DeviceNetTM buscoupler automatically configures, creating a local process image which may include analog, digital or specialty modules.
DeviceNetTM stores the process image in the corresponding Master control (PLC, PC or NC).
The local process image is divided into two data zones containing the data received and the data to be sent. The process data can be sent via the DeviceNetTM fieldbus to the PLC, PC or NC for further processing, and received from the field via DeviceNetTM.
The data of the analog modules is stored in the process image which is created automatically according to the order in which the modules are connected to the buscoupler. The bits of the digital modules are sent byte by byte and added to the analog data. If the amount of digital information exceeds 8 bits, the buscoupler automatically starts with a new byte.
Notice: EDS files required
Transmission medium:
Shielded Cu cable Trunk line: 2 x 0.82 mm2 + 2 x 1.7 mm2 Drop line: 2 x 0.2 mm2 + 2 x 0.32 mm2
Buscoupler connection:
5-pole male connector, 231 Series (MCS), female connector 231-305/ 010-000/050-000 (included)