750-585 2-ch Analog-Output Intrinsically safe 0-20mA 12Bit 2ms

Back| Overview|Product 106 of 107 in this category Prev|Next
750-585 2-ch Analog-Output Intrinsically safe 0-20mA 12Bit 2ms
For a larger view click on the thumbnail
750-585 2-ch Analog-Output Intrinsically safe 0-20mA 12Bit 2ms
750-585 2-ch Analog-Output Intrinsically safe 0-20mA 12Bit 2ms
Shipping time: 6 working days* 6 working days*
Stock quantity: 0 pcs. / order item
Product no.: 750-585
GTIN/EAN: 4045454725570
MPN: 750-585
Weight: 0.090 kg
Manufacturer: WagoMore products of: Wago
For further information, please visit the homepage of this product.
379,04 €
19 % VAT incl. excl. Shipping costs
Netto:318,52 €
* Valid for shipments within Germany.
Delivery times to other countries and information how to calculate see here


Wago

  • Details
  • Data sheet
  • Features

Products description

Wago 750-585 WAGO I/O-SYSTEM 750 Intrinsically safe Analog Output Module

 

2-Channel Analog-Output, Signal: DC 0-20 mA, Intrinsically safe, Actuator connection: 2x (2-conductor), Resolution: 12 Bit, Conversion time: 2 ms, Power consumption Pmax.: 1,5 W, measuring error: 0.2%, temperature error-max.: 0.01%/K, Intrinsically safety Ex i: yes, Linearity: +-2 LSB

 

General Description

The analog output module transmits intrinsically safe 0-20 mA signals in the hazardous areas of Zone 0+1.

The WAGO-I/O-SYSTEM 750 must be installed either in Zone 2 or in a non-hazardous area.

Power is derived from the power jumper contacts.

The outputs are short-circuit-protected.

LED: Green LED (output status)

Field and system levels are electrically isolated.

Note: The analog output module must only be operated via Ex i 24VDC power supply!

General information (e.g., installation regulations) on explosion protection is available in the WAGO-I/O-SYSTEM 750 manuals!

Voltage via power jumper contacts:

24 VDC (provided via Ex i supply UO = max. 27.3 V)

ATEX Guideline:

EN 60079-0, EN 60079-11, EN 60079-15, EN 60079-26, EN 60079-31

Marking:

II 3 (2) GD Ex nA tD [ib] [ibD] I/IIC / IIB A22 IP6X T135°C (T4)

Electric circuit, safety-relevant data:

Uo = 27.3 V , Io = 57.5 mA, Po = 392 mW, Characteristic: Linear

Datenblatt: 750-585 2-ch Analog-Output Intrinsically safe 0-20mA 12Bit 2ms

Product Features

Variant:Output
Connection:2-wire
No. of channels:2
Signal:0-20mA
Resolution:12 Bit
Conversion time:< 2 ms